Why your heat pump quote ignores the duct or pipe run entirely

By Priya Nathan · October 10, 2026 · 8 min read
Outdoor heat pump unit installation
Photo by alpha innotec on Unsplash

I was out at a place on Kooyong Road a few months back, quoting a replacement for a tired old split system, and the homeowner pulled out three quotes to compare. Same brand, same indoor head, near-identical kW rating. Line items for the unit itself were within a few hundred dollars of each other. Not one of the three mentioned the refrigerant line length, and the outdoor unit location in two of the three quotes would have meant a run close to double the length of the third. Nobody had walked the roof space. That's the bit that gets skipped, and it's the bit that actually determines what you pay to run the thing for the next fifteen years.

This is the heat pump sizing and installation mistake I reckon costs homeowners the most quietly, because it never shows up as an obvious failure. The system runs. It heats the house. It just costs more than it should, or it underperforms by a margin small enough that nobody complains loudly enough to get it looked at.

The quote prices the box, not the install

Most residential heat pump quotes are built around the equipment: a condensing unit, an indoor head or air handler, a line set up to some standard length, usually 5 to 7.5 metres. That standard length is baked into the manufacturer's performance figures too, including the capacity and the efficiency rating on the spec sheet. Once you install the unit with a longer run, every one of those figures starts to drift.

Refrigerant line length affects the system in two linked ways. First, there's a straightforward pressure drop issue, longer lines mean more friction loss in both the liquid and suction lines, and the refrigerant has to travel further to do its job. Second, and this is the one that catches people out, almost every manufacturer de-rates capacity and efficiency for runs beyond a baseline length, then de-rates again for every metre of vertical rise between indoor and outdoor units. A single-storey install with the outdoor unit tucked against the house is one problem. A two-storey home with the condenser on the ground and the head serving an upstairs bedroom is a different one, and the elevation change alone can knock several percentage points off the rated COP before the system has run for a single hour.

I've written before about how the COP number on the box isn't the COP you'll actually get, and line length is one of the biggest contributors to that gap. It doesn't get a line item on most quotes because installers price against the catalogue spec, not the site.

Ducted systems have the same problem, just bigger

With a ducted heat pump the equivalent issue is duct run length and static pressure, not refrigerant lines, but the effect on the homeowner is the same: invisible underperformance that nobody flags at quote stage. A ducted system sized against a Manual J (or AS/NZS 4859-style) load calculation assumes a certain external static pressure across the duct run. Add a few extra metres of flexible duct, a couple of unnecessary bends, or an undersized return air path, and the fan has to work harder to push the same airflow. That shows up as higher power draw at the blower, reduced airflow at distant registers, and a system that technically meets its rated capacity on paper while the back bedroom never quite gets warm.

This connects directly to something I covered in Manual J or gross feeling? Why heat pump load calcs still get skipped: the load calc tells you what capacity you need at the design temperature, but it says nothing about whether the ductwork can actually deliver that capacity to every room without a fight. Two houses with identical floor plans and identical heat pumps can perform completely differently depending on duct routing, insulation of the ducts themselves, and how many 90-degree bends the installer took because it was easier than going around a beam.

If you're deciding between a ducted and split-system approach in the first place, it's worth reading Ducted vs Split-System Heat Pumps: Which One Actually Fits Your Home before you get to the point of comparing quotes, because the duct-run penalty only applies to one of those two options.

Why installers don't flag it upfront

I don't think this is usually deliberate. Most installers quote from a standard template, walk the site briefly, and confirm the unit will fit and the circuit will handle it (a separate and very real problem I covered in the circuit sizing mistake that trips heat pump installs before day one). Measuring exact line length or modelling duct static pressure takes longer, and on a competitive residential quote, the installer who spends an extra forty minutes doing that work is often the installer who comes in a bit more expensive and loses the job to someone who didn't bother.

That's a structural problem with how heat pump installs get priced in both Australia and the US, and it's the sort of thing an inspector checking for a commissioning certificate would catch, if commissioning certificates were routinely done properly. In my experience they often aren't. The honest answer: ask for the refrigerant line length or duct run length to be written into the quote before you sign, with the manufacturer's de-rate table referenced against that exact length. A good installer will have this on hand because they've already worked out where the outdoor unit and indoor head are going. If they haven't settled on locations yet, they can't have priced the install accurately, full stop.

What a longer run actually costs you

The manufacturer's engineering data for most residential-scale heat pumps includes a capacity and efficiency correction table against line length and vertical separation. As a rough shape of the problem (exact figures vary by brand and model, so check the specific unit's engineering manual rather than taking a number from me): once you're past the baseline length, every additional few metres trims capacity by a small percentage and trims efficiency by a similar or slightly larger amount, with vertical rise typically penalised harder than horizontal run.

On a system like the Daikin Premium Inverter Ducted or the Zuba Central Ducted Heat Pump, both of which get specified for larger homes where long runs are more likely, that de-rate matters more in absolute terms because the systems are already working near their design capacity on cold mornings. A 5% capacity loss on an oversized residential split is barely noticeable. The same 5% loss on a correctly-sized system serving a whole house on a sub-zero morning is the difference between holding setpoint and the backup resistance element kicking in, which is exactly the running-cost blowout nobody budgeted for.

Over a heating season, that translates to more compressor runtime, more defrost cycles (not a fault, by the way, see the defrost cycle myth if you've wondered about that cold-air blast), and a noticeably higher power bill than the EnergyGuide or Zoned Energy Rating Label figure suggested. Those labels are tested at standard conditions, including standard line length, under ENERGY STAR's air-source heat pump testing criteria in the US or under the equivalent AS/NZS 3823 testing regime in Australia. A longer-than-standard install voids that comparison quietly, without anyone telling you.

What to actually check before you sign

Walk the proposed outdoor unit location and the proposed indoor head or ducted plenum location yourself, and ask the installer to measure (not estimate) the line or duct run between them, including any vertical rise. Ask them to write the de-rated capacity and COP for that specific length into the quote, not just the nameplate figures. If the installer can't produce that de-rate figure, ask which manufacturer engineering document they'd use to find it, because every major brand publishes one.

For ducted systems specifically, ask whether the design includes a static pressure calculation for the actual duct layout, not a generic assumption. This is standard practice under good HVAC design discipline, and it's referenced in the ACCA Manual D methodology in the US for duct design, alongside Manual J for loads. In Australia the closest equivalent sits within AS 4254 for ductwork and the AIRAH DA19 application manual, though plenty of residential installers skip formal duct design altogether and size runs by habit. That's not malicious, it's just not good enough on a borderline-length run.

I'll be honest about where I land on this: I think line length and duct design should be a mandatory line item on every residential heat pump quote, the same way the electrical circuit sizing should be. It isn't currently standard practice in either market, and until it is, the burden sits on the homeowner to ask the awkward question before signing.

A quick gut check for existing systems

If you've already got a heat pump installed and you're wondering whether this applies to you, a rough visual check helps. Walk the refrigerant line set from outdoor unit to indoor head and count the bends and the approximate metres; anything over roughly 10-15 metres on a residential split, or any run with more than a few metres of vertical rise, is worth asking your installer or a second opinion about. For ducted systems, a noticeably weak register in the room furthest from the air handler, especially if it's always the coldest room in winter, is a classic symptom of a duct run that's too long, too restrictive, or poorly insulated for the distance it covers.

None of this means longer runs are impossible or that you need to relocate your outdoor unit to the nearest wall. Plenty of installs genuinely need a longer line, particularly on larger blocks or multi-storey homes. The point is that the cost of that longer run should show up in the quote and in the expected running cost, not as a mystery bump on your power bill eighteen months in.

— Priya Nathan, Heat Pumps & HVAC, IceWarm

Tagged

Common questions

How long can a refrigerant line run before it hurts performance?
It depends on the specific unit, but most residential split systems are rated at a baseline of around 5 to 7.5 metres before manufacturer de-rate tables kick in. Beyond that, both capacity and efficiency drop, and vertical rise between indoor and outdoor units is usually penalised more heavily than horizontal distance. Check the specific model's engineering manual rather than assuming a generic figure.
Does duct length matter as much as refrigerant line length?
For ducted systems, yes, though the mechanism is different. Longer or more convoluted duct runs increase static pressure, which makes the blower work harder and can reduce airflow to rooms furthest from the air handler. It shows up as uneven comfort and higher power draw rather than a straightforward capacity de-rate.
Should I ask for the line length de-rate in writing before signing a quote?
Yes. Any installer pricing an install accurately has already decided roughly where the outdoor unit and indoor head will sit, so they can measure the run and reference the manufacturer's de-rated capacity and COP for that length. If they can't provide it, the quote is based on nameplate figures that may not reflect what you'll actually get.
Can a longer line run be fixed after installation?
Sometimes relocating the outdoor unit closer, or reducing unnecessary bends in the line set, can help, but refrigerant line length is largely a design decision made at install. For ducted systems, sealing and insulating existing ducts and removing unnecessary bends can recover some lost performance without a full redesign.